Specifications
AC Horsepower Ratings
- At Rated Voltage: 1/2 HP
Electrical Specifications
- Amperage: 15 Amp
- Current Limiting: Full Rated Current
- Dielectric Voltage: Withstands 2000V per UL498
- Grounding: Isolated Ground
- Pole: 2
- Temperature Rise: Max 30C after 250 cycles OL at 200 percent rated current
- Voltage: 125 Volt
- Wire: 3
Environmental Specifications
- Flammability: Rated V-2 per UL94
- Operating Temperature: -40C-60C
Material Specifications
- Body Material: Nylon
- Clamp Nuts: Zinc-Plated Steel
- Color: Gray
- Face Material: Nylon
- Grounding Screw: Brass 8-32
- Strap Material: Steel
- Terminal Screws: Brass 10-32
- Yoke: Zinc-Plated Steel
Mechanical Specifications
- Product ID: Ratings are permanently marked on device
- Terminal Accom.: 14-10 AWG
- Terminal ID: Brass-Hot, Green-Ground, Silver-Neutral
- Termination: Back & Side
Product Features
- Color: Gray
- Grade: Hospital
- NEMA: 5-15R
Standards and Certifications
- ANSI: C-73
- CSA C22.2 No. 42: File 152105
- NEMA: WD-6
- NOM: 057
- UL498HG: File E13399
- Warranty: 10-Year Limited
Related Products
- 16262-IG
- 16262-IGB
- 16262-IGE
- 16262-IGI
- 16262-IGR
- 16262-IGT
- 16262-IGW
Downloads
Dimensional DataWiring Diagram
Videos
Decora
More Information
Manufacturer Catalog Number
16262-IGG
Weight
12.6000
Material
Nylon
Color
Gray
Amperage
15 amperes
Dielectric
2000 volts
Flammability Class
Rated V-2 Per UL94
Grade
Hospital
Grounding
Isolated Ground
Nema
5-15R
Number Of Poles
2
Number Of Wires
3
Operating Temperature
-40 To 60 degrees celsius
Temperature Rise
Max 30C After 250 Cycles OL At 200 Percent Rated Current
Terminal Type
Brass-Hot, Green-Ground, Silver-Neutral
Voltage
125 volts
Warranty Length