Description
Specifications
- Type: UA
- Electrical Trade Size: 3/4 in (21 mm)
- Length: 100 ft (30.48 m)
- Packaging: Small Cartons
- Inside Diameter: 0.820 to 0.840 in (20.828 to 21.336 mm)
- Outside Diameter: 1.030 to 1.050 in (26.162 to 26.670 mm)
- Approx. Inside Bend Radius: 5 in (127 mm)
- Approx. Weight per 100 ft: 44 lbs (19.96 kg)
- Color: Gray
- Optional Colors: Black
- Certifications: UL Listed & CSA Certified
- Cross-Reference #: 22101, 55-08-27-03, 6203-30-00, LA-12, UALT-3/4
Installation
- Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
- Approved for both exposed and concealed locations. Rated for temperature ranges -40ºF to + 176ºF (-40ºC to +80ºC).
- Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
- Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
- Manufactured in a full range of trade sizes from 3/8" through 4".
- Approved for direct burial and in concrete trade sizes 3/8" through 4".
- Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.
NEC Articles
- Article 250.118 (6) Equipment Grounding
- Article 300.22 (D) Information Technology Equipment
- Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
- Article 501.10 (B) (2) Class I Div. 2
- Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
- Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
- Article 620.21 Elevator Wiring Methods
- Article 645.5 (E) (2) Under Raised Floors
Application
- Where UL Listing is Required and Conduit Grounding is Necessary
- Temperature Range: -40ºF to +176ºF (-40ºC to +80ºC)
Downloads
Spec SheetChemical Resistance Chart
Packaging, Cutting Instructions, Custom Cut Lengths
Type UA Datasheet
3/4" UAG MSDS