Description
Features
- The Leviton Provolt™ Dual Relay Occupancy Sensors combine line voltage occupancy sensors and photocells into a self-contained unit. The integrated design alleviates the need for separate power pack and occupancy sensor wiring making it a low-cost, efficient energy solution for new construction and retrofits.
- Utilizes sensors which emit non-audible sound waves and sense movement. Any movement within the sensor’s field-of-view causes a shift in the original emitted frequency. The sensor identifies the change as movement and controls light accordingly. U/S models are immune to external ultrasonic signals from other sources such as white-boards delivering uninterrupted performance.
- Auto-Adapting: Time delay and sensitivity are continually adjusted to occupancy pattern of use
- Vacancy Sensing Time Outs: (Delayed OFF Timer, Exclusive Walk-through Feature, Time delay and saved settings are protected during power outages and will return to the last known state)
- Output short circuit protection
- Industry-exclusive self-configuring local manual switch input: Momentary or maintained switches are supported
- Presentation Mode allows user to turn lights OFF and keep them OFF while the room is occupied
- Adjustable Time Delay: 30s, 5min, 10min, 20min, 30min
- Test Mode for simplified commissioning
- Manual Switch and Emergency Override are Class 1 or Class 2 circuits. Class 2 circuits provided for flexibility
- Industry-exclusive “fail-safe” circuitry: In the event of product failure, Return-to-Closed feature causes the relay to default ON which eliminates life safety concerns
- Industry-exclusive H.I.S. (High Inrush Stability) technology designed to handle today’s high inrush electronic ballast loads and offer unmatched durability and service
- Robust and reliable mechanically held 10A latching relay provides dependability and robust performance for all load types and provides energy savings over electronically held relays
- Field of View: Units from 500 to 2000 square feet available
- Visual LED indicators for all states: (Green - Blinks during U/S detection and is solid during auto-calibration, Yellow - Blinks during test mode; solid with emergency/BMS input, Blue - Blinks when knob settings are changed and during photocell override
Color Variations
- White
Specifications
- Country of Origin: China
- RoHS Compliant: Yes
Product Features
- Application: Code Compliance, Auto ON/Auto OFF, Manual ON/Auto OFF, Fan Control, Auto ON/Manual ON, Stairwell Control, Step dimming
- Color: White
- Feature: Multi-Technology Line Voltage Dual Relay
- Grade: Commercial
- Mounting: Ceiling Mount
- Product Line: Provolt
- Sensor Technology: Multi-Technology: Passive Infrared (PIR)/Ultrasonic (US)
- Sensor Type: Occupancy, Photocell
- Time Delay: 30s-30m
- Title 24 Compliant: Yes
Performance Specifications
- Coverage (Sq.Ft.): 1000
- Pattern: 360°
Electrical Specifications
- Current Consumption: 60-30mA
- Frequency: 50/60Hz
- Load Rating: 120V, 50/60Hz: 8A, Electronic Ballast, 800W, Tungsten, 800VA Ballast, 1/4 HP Motor - 230V, 50Hz: 6A/6AX, Electronic Ballast, Magnetic Ballast, Tungsten, 1/3 HP Motor - 277V, 50/60Hz: 5A, Electronic Ballast, 1200VA Ballast, 1/3 HP Motor
- Neutral Wire Connection: Required
- Voltage: 120/230/277 VAC
Standards and Certifications
- Listings: Can be used to comply with ASHRAE 90.1 and Title 24, Part 6 occupancy/vacancy sensing, automatic shutoff, daylight harvesting and stairwell control requirements, UL 773A (Occupancy Standard), UL 924 (Emergency Equipment), cUL listed, CE compliant, NOM certified, RoHS compliant, NY LLC48 compliant
Mechanical Specifications
- Mounting Type: Ceiling Mount
- Relay Type: Dual Relay
- Size: Width 4.80" (121.92mm), Depth 2.39" (60.71mm)
Environmental Specifications
- Operating Temperature: 32° to 104°F (0° to 40°C)
- Relative Humidity: 0% to 90% non-condensing
- Storage Temperature Range: -15° to 160°F (-26° to 71°C)
Type
- Product Type: Occupancy Sensor and Photocell
Warranty
- Warranty: 5-Year Limited
Downloads
Spec SheetApplication Note
Application_Note-ODC_Series_Dual_Relay_Occupancy_Sensors.pdfInstruction Sheet
PK-93872-10-00-2D-W.pdfPK-93872-10-05-2D-W.pdf
PK-93872-10-04-2D-W.pdf
Videos
More Information
Manufacturer Catalog Number
O2C10-MDW
Weight
8.6900
Country of Origin
China
Color
White
Frequency
50 hertz
Grade
Commercial
Mounting Type
Ceiling
Operating Temperature
0 degrees
Product Size
121.92 millimeters
Warranty Length
5 years